Filtered by vendor Wago Subscriptions
Filtered by product 750-8208 Subscriptions
Total 6 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2023-1619 1 Wago 152 750-331, 750-331 Firmware, 750-8202 and 149 more 2023-07-11 4.9 Medium
Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a malformed packet.
CVE-2023-1620 1 Wago 152 750-331, 750-331 Firmware, 750-8202 and 149 more 2023-07-11 4.9 Medium
Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime.
CVE-2022-3281 1 Wago 156 750-8100, 750-8100 Firmware, 750-8101 and 153 more 2022-11-04 7.5 High
WAGO Series PFC100/PFC200, Series Touch Panel 600, Compact Controller CC100 and Edge Controller in multiple versions are prone to a loss of MAC-Address-Filtering after reboot. This may allow an remote attacker to circumvent the reach the network that should be protected by the MAC address filter.
CVE-2021-21000 1 Wago 54 750-8202, 750-8202 Firmware, 750-8203 and 51 more 2021-05-28 7.5 High
On WAGO PFC200 devices in different firmware versions with special crafted packets an attacker with network access to the device could cause a denial of service for the login service of the runtime.
CVE-2021-21001 1 Wago 54 750-8202, 750-8202 Firmware, 750-8203 and 51 more 2021-05-28 6.5 Medium
On WAGO PFC200 devices in different firmware versions with special crafted packets an authorised attacker with network access to the device can access the file system with higher privileges.
CVE-2018-5459 1 Wago 19 750-8202, 750-8202\/025-000, 750-8202\/025-001 and 16 more 2019-10-09 N/A
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.