Filtered by vendor Schneider-electric Subscriptions
Total 732 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2022-22804 1 Schneider-electric 1 Ecostruxure Power Monitoring Expert 2022-02-10 5.4 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could allow an authenticated attacker to view data, change settings, or impact availability of the software when the user visits a page containing the injected payload. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior)
CVE-2022-22726 1 Schneider-electric 1 Ecostruxure Power Monitoring Expert 2022-02-10 6.5 Medium
A CWE-20: Improper Input Validation vulnerability exists that could allow arbitrary files on the server to be read by authenticated users through a limited operating system service account. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior)
CVE-2022-22725 1 Schneider-electric 2 Easergy P3, Easergy P3 Firmware 2022-02-10 8.8 High
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P3 (All versions prior to V30.205)
CVE-2022-22723 1 Schneider-electric 2 Easergy P5, Easergy P5 Firmware 2022-02-10 8.8 High
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101)
CVE-2022-22722 1 Schneider-electric 2 Easergy P5, Easergy P5 Firmware 2022-02-10 7.5 High
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could result in information disclosure. If an attacker were to obtain the SSH cryptographic key for the device and take active control of the local operational network connected to the product they could potentially observe and manipulate traffic associated with product configuration. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101)
CVE-2021-22814 1 Schneider-electric 55 Ap9922 Battery Management System, Apc Rack Power Distribution Units, Galaxy 3500 and 52 more 2022-02-04 6.1 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists which could cause arbritrary script execution when a malicious file is read and displayed. Affected Products: 1-Phase Uninterruptible Power Supply (UPS) using NMC2 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.8 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 250/500 (SYPX) Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.6 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 48/96/100/160 kW UPS (PX2), Symmetra PX 20/40 kW UPS (SY3P), Gutor (SXW, GVX), and Galaxy (GVMTS, GVMSA, GVXTS, GVXSA, G7K, GFC, G9KCHU): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635CH (NMC2 AOS V6.9.6 and earlier), 1-Phase Uninterruptible Power Supply (UPS) using NMC3 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 3 (NMC3): AP9640/AP9640J, AP9641/AP9641J, AP9643/AP9643J (NMC3 AOS V1.4.2.1 and earlier), APC Rack Power Distribution Units (PDU) using NMC2 2G Metered/Switched Rack PDUs with embedded NMC2: AP84XX, AP86XX, AP88XX, AP89XX (NMC2 AOS V6.9.6 and earlier), APC Rack Power Distribution Units (PDU) using NMC3 2G Metered/Switched Rack PDUs with embedded NMC3: APDU99xx (NMC3 AOS V1.4.0 and earlier), APC 3-Phase Power Distribution Products using NMC2 Galaxy RPP: GRPPIP2X84 (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) for InfraStruxure 150 kVA PDU with 84 Poles (X84P): PDPB150G6F (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for InfraStruxure 40/60kVA PDU (XPDU) PD40G6FK1-M, PD40F6FK1-M, PD40L6FK1-M, PDRPPNX10 M,PD60G6FK1, PD60F6FK1, PD60L6FK1, PDRPPNX10, PD40E5EK20-M, PD40H5EK20-M (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular 150/175kVA PDU (XRDP): PDPM150G6F, PDPM150L6F, PDPM175G6H (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for 400 and 500 kVA (PMM): PMM400-ALA, PMM400-ALAX, PMM400-CUB, PMM500-ALA, PMM500-ALAX, PMM500-CUB (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular PDU (XRDP2G): PDPM72F-5U, PDPM138H-5U, PDPM144F, PDPM138H-R, PDPM277H, PDPM288G6H (NMC2 AOS V6.9.6 and earlier), Rack Automatic Transfer Switches (ATS) Embedded NMC2: Rack Automatic Transfer Switches - AP44XX (ATS4G) (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) Cooling Products: InRow Cooling for series ACRP5xx, ACRP1xx, ACRD5xx, and ACRC5xx SKUs (ACRP2G), InRow Cooling for series ACRC10x SKUs (RC10X2G), InRow Cooling for series ACRD6xx and ACRC6xx SKUs (ACRD2G), InRow Cooling Display for series ACRD3xx (ACRC2G), InRow Cooling for series ACSC1xx SKUs (SC2G), InRow Cooling for series ACRD1xx and ACRD2xx (ACRPTK2G), Ecoflair IAEC25/50 Air Economizer Display (EB2G), Uniflair SP UCF0481I, UCF0341I (UNFLRSP), Uniflair LE DX Perimeter Cooling Display for SKUs: IDAV, IDEV, IDWV, IUAV, IUEV, IUWV, IXAV, IXEV, IXWV, LDAV, LDEV, and LDWV (LEDX2G), Refrigerant Distribution Unit: ACDA9xx (RDU) (NMC2 AOS V6.9.6 and earlier), Environmental Monitoring Unit with embedded NMC2 (NB250): NetBotz NBRK0250 (NMC2 AOS V6.9.6 and earlier), and Network Management Card 2 (NMC2): AP9922 Battery Management System (BM4) (NMC2 AOS V6.9.6 and earlier)
CVE-2021-22813 1 Schneider-electric 55 Ap9922 Battery Management System, Apc Rack Power Distribution Units, Galaxy 3500 and 52 more 2022-02-04 6.1 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause arbritrary script execution when a privileged account clicks on a malicious URL specifically crafted for the NMC pointing to an edit policy file. Affected Products: 1-Phase Uninterruptible Power Supply (UPS) using NMC2 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.8 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 250/500 (SYPX) Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.6 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 48/96/100/160 kW UPS (PX2), Symmetra PX 20/40 kW UPS (SY3P), Gutor (SXW, GVX), and Galaxy (GVMTS, GVMSA, GVXTS, GVXSA, G7K, GFC, G9KCHU): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635CH (NMC2 AOS V6.9.6 and earlier), 1-Phase Uninterruptible Power Supply (UPS) using NMC3 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 3 (NMC3): AP9640/AP9640J, AP9641/AP9641J, AP9643/AP9643J (NMC3 AOS V1.4.2.1 and earlier), APC Rack Power Distribution Units (PDU) using NMC2 2G Metered/Switched Rack PDUs with embedded NMC2: AP84XX, AP86XX, AP88XX, AP89XX (NMC2 AOS V6.9.6 and earlier), APC Rack Power Distribution Units (PDU) using NMC3 2G Metered/Switched Rack PDUs with embedded NMC3: APDU99xx (NMC3 AOS V1.4.0 and earlier), APC 3-Phase Power Distribution Products using NMC2 Galaxy RPP: GRPPIP2X84 (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) for InfraStruxure 150 kVA PDU with 84 Poles (X84P): PDPB150G6F (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for InfraStruxure 40/60kVA PDU (XPDU) PD40G6FK1-M, PD40F6FK1-M, PD40L6FK1-M, PDRPPNX10 M,PD60G6FK1, PD60F6FK1, PD60L6FK1, PDRPPNX10, PD40E5EK20-M, PD40H5EK20-M (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular 150/175kVA PDU (XRDP): PDPM150G6F, PDPM150L6F, PDPM175G6H (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for 400 and 500 kVA (PMM): PMM400-ALA, PMM400-ALAX, PMM400-CUB, PMM500-ALA, PMM500-ALAX, PMM500-CUB (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular PDU (XRDP2G): PDPM72F-5U, PDPM138H-5U, PDPM144F, PDPM138H-R, PDPM277H, PDPM288G6H (NMC2 AOS V6.9.6 and earlier), Rack Automatic Transfer Switches (ATS) Embedded NMC2: Rack Automatic Transfer Switches - AP44XX (ATS4G) (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) Cooling Products: InRow Cooling for series ACRP5xx, ACRP1xx, ACRD5xx, and ACRC5xx SKUs (ACRP2G), InRow Cooling for series ACRC10x SKUs (RC10X2G), InRow Cooling for series ACRD6xx and ACRC6xx SKUs (ACRD2G), InRow Cooling Display for series ACRD3xx (ACRC2G), InRow Cooling for series ACSC1xx SKUs (SC2G), InRow Cooling for series ACRD1xx and ACRD2xx (ACRPTK2G), Ecoflair IAEC25/50 Air Economizer Display (EB2G), Uniflair SP UCF0481I, UCF0341I (UNFLRSP), Uniflair LE DX Perimeter Cooling Display for SKUs: IDAV, IDEV, IDWV, IUAV, IUEV, IUWV, IXAV, IXEV, IXWV, LDAV, LDEV, and LDWV (LEDX2G), Refrigerant Distribution Unit: ACDA9xx (RDU) (NMC2 AOS V6.9.6 and earlier), Environmental Monitoring Unit with embedded NMC2 (NB250): NetBotz NBRK0250 (NMC2 AOS V6.9.6 and earlier), and Network Management Card 2 (NMC2): AP9922 Battery Management System (BM4) (NMC2 AOS V6.9.6 and earlier)
CVE-2021-22812 1 Schneider-electric 55 Ap9922 Battery Management System, Apc Rack Power Distribution Units, Galaxy 3500 and 52 more 2022-02-04 6.1 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause arbritrary script execution when a privileged account clicks on a malicious URL specifically crafted for the NMC. Affected Products: 1-Phase Uninterruptible Power Supply (UPS) using NMC2 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.8 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 250/500 (SYPX) Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.6 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 48/96/100/160 kW UPS (PX2), Symmetra PX 20/40 kW UPS (SY3P), Gutor (SXW, GVX), and Galaxy (GVMTS, GVMSA, GVXTS, GVXSA, G7K, GFC, G9KCHU): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635CH (NMC2 AOS V6.9.6 and earlier), 1-Phase Uninterruptible Power Supply (UPS) using NMC3 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 3 (NMC3): AP9640/AP9640J, AP9641/AP9641J, AP9643/AP9643J (NMC3 AOS V1.4.2.1 and earlier), APC Rack Power Distribution Units (PDU) using NMC2 2G Metered/Switched Rack PDUs with embedded NMC2: AP84XX, AP86XX, AP88XX, AP89XX (NMC2 AOS V6.9.6 and earlier), APC Rack Power Distribution Units (PDU) using NMC3 2G Metered/Switched Rack PDUs with embedded NMC3: APDU99xx (NMC3 AOS V1.4.0 and earlier), APC 3-Phase Power Distribution Products using NMC2 Galaxy RPP: GRPPIP2X84 (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) for InfraStruxure 150 kVA PDU with 84 Poles (X84P): PDPB150G6F (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for InfraStruxure 40/60kVA PDU (XPDU) PD40G6FK1-M, PD40F6FK1-M, PD40L6FK1-M, PDRPPNX10 M,PD60G6FK1, PD60F6FK1, PD60L6FK1, PDRPPNX10, PD40E5EK20-M, PD40H5EK20-M (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular 150/175kVA PDU (XRDP): PDPM150G6F, PDPM150L6F, PDPM175G6H (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for 400 and 500 kVA (PMM): PMM400-ALA, PMM400-ALAX, PMM400-CUB, PMM500-ALA, PMM500-ALAX, PMM500-CUB (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular PDU (XRDP2G): PDPM72F-5U, PDPM138H-5U, PDPM144F, PDPM138H-R, PDPM277H, PDPM288G6H (NMC2 AOS V6.9.6 and earlier), Rack Automatic Transfer Switches (ATS) Embedded NMC2: Rack Automatic Transfer Switches - AP44XX (ATS4G) (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) Cooling Products: InRow Cooling for series ACRP5xx, ACRP1xx, ACRD5xx, and ACRC5xx SKUs (ACRP2G), InRow Cooling for series ACRC10x SKUs (RC10X2G), InRow Cooling for series ACRD6xx and ACRC6xx SKUs (ACRD2G), InRow Cooling Display for series ACRD3xx (ACRC2G), InRow Cooling for series ACSC1xx SKUs (SC2G), InRow Cooling for series ACRD1xx and ACRD2xx (ACRPTK2G), Ecoflair IAEC25/50 Air Economizer Display (EB2G), Uniflair SP UCF0481I, UCF0341I (UNFLRSP), Uniflair LE DX Perimeter Cooling Display for SKUs: IDAV, IDEV, IDWV, IUAV, IUEV, IUWV, IXAV, IXEV, IXWV, LDAV, LDEV, and LDWV (LEDX2G), Refrigerant Distribution Unit: ACDA9xx (RDU) (NMC2 AOS V6.9.6 and earlier), Environmental Monitoring Unit with embedded NMC2 (NB250): NetBotz NBRK0250 (NMC2 AOS V6.9.6 and earlier), and Network Management Card 2 (NMC2): AP9922 Battery Management System (BM4) (NMC2 AOS V6.9.6 and earlier)
CVE-2020-7568 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2022-02-04 4.3 Medium
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.
CVE-2020-7567 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2022-02-04 5.7 Medium
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys.
CVE-2021-22811 1 Schneider-electric 55 Ap9922 Battery Management System, Apc Rack Power Distribution Units, Galaxy 3500 and 52 more 2022-02-04 6.1 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause script execution when the request of a privileged account accessing the vulnerable web page is intercepted. Affected Products: 1-Phase Uninterruptible Power Supply (UPS) using NMC2 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.8 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 250/500 (SYPX) Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.6 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 48/96/100/160 kW UPS (PX2), Symmetra PX 20/40 kW UPS (SY3P), Gutor (SXW, GVX), and Galaxy (GVMTS, GVMSA, GVXTS, GVXSA, G7K, GFC, G9KCHU): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635CH (NMC2 AOS V6.9.6 and earlier), 1-Phase Uninterruptible Power Supply (UPS) using NMC3 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 3 (NMC3): AP9640/AP9640J, AP9641/AP9641J, AP9643/AP9643J (NMC3 AOS V1.4.2.1 and earlier), APC Rack Power Distribution Units (PDU) using NMC2 2G Metered/Switched Rack PDUs with embedded NMC2: AP84XX, AP86XX, AP88XX, AP89XX (NMC2 AOS V6.9.6 and earlier), APC Rack Power Distribution Units (PDU) using NMC3 2G Metered/Switched Rack PDUs with embedded NMC3: APDU99xx (NMC3 AOS V1.4.0 and earlier), APC 3-Phase Power Distribution Products using NMC2 Galaxy RPP: GRPPIP2X84 (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) for InfraStruxure 150 kVA PDU with 84 Poles (X84P): PDPB150G6F (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for InfraStruxure 40/60kVA PDU (XPDU) PD40G6FK1-M, PD40F6FK1-M, PD40L6FK1-M, PDRPPNX10 M,PD60G6FK1, PD60F6FK1, PD60L6FK1, PDRPPNX10, PD40E5EK20-M, PD40H5EK20-M (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular 150/175kVA PDU (XRDP): PDPM150G6F, PDPM150L6F, PDPM175G6H (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for 400 and 500 kVA (PMM): PMM400-ALA, PMM400-ALAX, PMM400-CUB, PMM500-ALA, PMM500-ALAX, PMM500-CUB (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular PDU (XRDP2G): PDPM72F-5U, PDPM138H-5U, PDPM144F, PDPM138H-R, PDPM277H, PDPM288G6H (NMC2 AOS V6.9.6 and earlier), Rack Automatic Transfer Switches (ATS) Embedded NMC2: Rack Automatic Transfer Switches - AP44XX (ATS4G) (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) Cooling Products: InRow Cooling for series ACRP5xx, ACRP1xx, ACRD5xx, and ACRC5xx SKUs (ACRP2G), InRow Cooling for series ACRC10x SKUs (RC10X2G), InRow Cooling for series ACRD6xx and ACRC6xx SKUs (ACRD2G), InRow Cooling Display for series ACRD3xx (ACRC2G), InRow Cooling for series ACSC1xx SKUs (SC2G), InRow Cooling for series ACRD1xx and ACRD2xx (ACRPTK2G), Ecoflair IAEC25/50 Air Economizer Display (EB2G), Uniflair SP UCF0481I, UCF0341I (UNFLRSP), Uniflair LE DX Perimeter Cooling Display for SKUs: IDAV, IDEV, IDWV, IUAV, IUEV, IUWV, IXAV, IXEV, IXWV, LDAV, LDEV, and LDWV (LEDX2G), Refrigerant Distribution Unit: ACDA9xx (RDU) (NMC2 AOS V6.9.6 and earlier), Environmental Monitoring Unit with embedded NMC2 (NB250): NetBotz NBRK0250 (NMC2 AOS V6.9.6 and earlier), and Network Management Card 2 (NMC2): AP9922 Battery Management System (BM4) (NMC2 AOS V6.9.6 and earlier)
CVE-2021-22810 1 Schneider-electric 55 Ap9922 Battery Management System, Apc Rack Power Distribution Units, Galaxy 3500 and 52 more 2022-02-04 6.1 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause arbritrary script execution when a privileged account clicks on a malicious URL specifically crafted for the NMC pointing to a delete policy file. Affected Products: 1-Phase Uninterruptible Power Supply (UPS) using NMC2 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.8 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 250/500 (SYPX) Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.6 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 48/96/100/160 kW UPS (PX2), Symmetra PX 20/40 kW UPS (SY3P), Gutor (SXW, GVX), and Galaxy (GVMTS, GVMSA, GVXTS, GVXSA, G7K, GFC, G9KCHU): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635CH (NMC2 AOS V6.9.6 and earlier), 1-Phase Uninterruptible Power Supply (UPS) using NMC3 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 3 (NMC3): AP9640/AP9640J, AP9641/AP9641J, AP9643/AP9643J (NMC3 AOS V1.4.2.1 and earlier), APC Rack Power Distribution Units (PDU) using NMC2 2G Metered/Switched Rack PDUs with embedded NMC2: AP84XX, AP86XX, AP88XX, AP89XX (NMC2 AOS V6.9.6 and earlier), APC Rack Power Distribution Units (PDU) using NMC3 2G Metered/Switched Rack PDUs with embedded NMC3: APDU99xx (NMC3 AOS V1.4.0 and earlier), APC 3-Phase Power Distribution Products using NMC2 Galaxy RPP: GRPPIP2X84 (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) for InfraStruxure 150 kVA PDU with 84 Poles (X84P): PDPB150G6F (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for InfraStruxure 40/60kVA PDU (XPDU) PD40G6FK1-M, PD40F6FK1-M, PD40L6FK1-M, PDRPPNX10 M,PD60G6FK1, PD60F6FK1, PD60L6FK1, PDRPPNX10, PD40E5EK20-M, PD40H5EK20-M (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular 150/175kVA PDU (XRDP): PDPM150G6F, PDPM150L6F, PDPM175G6H (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for 400 and 500 kVA (PMM): PMM400-ALA, PMM400-ALAX, PMM400-CUB, PMM500-ALA, PMM500-ALAX, PMM500-CUB (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular PDU (XRDP2G): PDPM72F-5U, PDPM138H-5U, PDPM144F, PDPM138H-R, PDPM277H, PDPM288G6H (NMC2 AOS V6.9.6 and earlier), Rack Automatic Transfer Switches (ATS) Embedded NMC2: Rack Automatic Transfer Switches - AP44XX (ATS4G) (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) Cooling Products: InRow Cooling for series ACRP5xx, ACRP1xx, ACRD5xx, and ACRC5xx SKUs (ACRP2G), InRow Cooling for series ACRC10x SKUs (RC10X2G), InRow Cooling for series ACRD6xx and ACRC6xx SKUs (ACRD2G), InRow Cooling Display for series ACRD3xx (ACRC2G), InRow Cooling for series ACSC1xx SKUs (SC2G), InRow Cooling for series ACRD1xx and ACRD2xx (ACRPTK2G), Ecoflair IAEC25/50 Air Economizer Display (EB2G), Uniflair SP UCF0481I, UCF0341I (UNFLRSP), Uniflair LE DX Perimeter Cooling Display for SKUs: IDAV, IDEV, IDWV, IUAV, IUEV, IUWV, IXAV, IXEV, IXWV, LDAV, LDEV, and LDWV (LEDX2G), Refrigerant Distribution Unit: ACDA9xx (RDU) (NMC2 AOS V6.9.6 and earlier), Environmental Monitoring Unit with embedded NMC2 (NB250): NetBotz NBRK0250 (NMC2 AOS V6.9.6 and earlier), and Network Management Card 2 (NMC2): AP9922 Battery Management System (BM4) (NMC2 AOS V6.9.6 and earlier)
CVE-2021-22818 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2022-02-03 7.5 High
A CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to gain unauthorized access to the charging station web interface by performing brute force attacks. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
CVE-2021-22820 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2022-02-03 9.8 Critical
A CWE-614 Insufficient Session Expiration vulnerability exists that could allow an attacker to maintain an unauthorized access over a hijacked session to the charger station web server even after the legitimate user account holder has changed his password. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
CVE-2021-22819 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2022-02-03 4.3 Medium
A CWE-1021 Improper Restriction of Rendered UI Layers or Frames vulnerability exists that could cause unintended modifications of the product settings or user accounts when deceiving the user to use the web interface rendered within iframes. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
CVE-2021-22821 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2022-02-03 8.6 High
A CWE-918 Server-Side Request Forgery (SSRF) vulnerability exists that could cause the station web server to forward requests to unintended network targets when crafted malicious parameters are submitted to the charging station web server. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
CVE-2021-22825 1 Schneider-electric 4 Rack Power Distribution Unit With Network Management Card 2, Rack Power Distribution Unit With Network Management Card 2 Firmware, Rack Power Distribution Unit With Network Management Card 3 and 1 more 2022-02-03 8.0 High
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could allow an attacker to access the system with elevated privileges when a privileged account clicks on a malicious URL that compromises the security token. Affected Products: AP7xxxx and AP8xxx with NMC2 (V6.9.6 or earlier), AP7xxx and AP8xxx with NMC3 (V1.1.0.3 or earlier), and APDU9xxx with NMC3 (V1.0.0.28 or earlier)
CVE-2021-22713 1 Schneider-electric 21 Ion7650 Firmware, Powerlogic Ion7300, Powerlogic Ion7300 Firmware and 18 more 2022-02-03 7.5 High
A CWE-119:Improper restriction of operations within the bounds of a memory buffer vulnerability exists in PowerLogic ION8650, ION8800, ION7650, ION7700/73xx, and ION83xx/84xx/85xx/8600 (see security notifcation for affected versions), which could cause the meter to reboot.
CVE-2021-22714 1 Schneider-electric 6 Powerlogic Ion7400, Powerlogic Ion7400 Firmware, Powerlogic Ion9000 and 3 more 2022-02-03 9.8 Critical
A CWE-119:Improper restriction of operations within the bounds of a memory buffer vulnerability exists in PowerLogic ION7400, PM8000 and ION9000 (All versions prior to V3.0.0), which could cause the meter to reboot or allow for remote code execution.
CVE-2021-22703 1 Schneider-electric 20 Powerlogic Ion7400, Powerlogic Ion7400 Firmware, Powerlogic Ion7650 and 17 more 2022-02-03 7.5 High
A CWE-319: Cleartext transmission of sensitive information vulnerability exists in PowerLogic ION7400, ION7650, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions), that could cause disclosure of user credentials when a malicious actor intercepts HTTP network traffic between a user and the device.