Filtered by vendor Schneider-electric
Subscriptions
Total
732 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2021-30066 | 2 Belden, Schneider-electric | 26 Eagle 20 Tofino 943 987-501-tx\/tx, Eagle 20 Tofino 943 987-501-tx\/tx Firmware, Eagle 20 Tofino 943 987-502 -tx\/mm and 23 more | 2022-04-09 | 6.8 Medium |
On Schneider Electric ConneXium Tofino Firewall TCSEFEA23F3F22 before 03.23, TCSEFEA23F3F20/21, and Belden Tofino Xenon Security Appliance, an arbitrary firmware image can be loaded because firmware signature verification (for a USB stick) can be bypassed. NOTE: this issue exists because of an incomplete fix of CVE-2017-11400. | ||||
CVE-2021-30065 | 2 Belden, Schneider-electric | 26 Eagle 20 Tofino 943 987-501-tx\/tx, Eagle 20 Tofino 943 987-501-tx\/tx Firmware, Eagle 20 Tofino 943 987-502 -tx\/mm and 23 more | 2022-04-09 | 7.5 High |
On Schneider Electric ConneXium Tofino Firewall TCSEFEA23F3F22 before 03.23, TCSEFEA23F3F20/21, and Belden Tofino Xenon Security Appliance, crafted ModBus packets can bypass the ModBus enforcer. NOTE: this issue exists because of an incomplete fix of CVE-2017-11401. | ||||
CVE-2021-30063 | 2 Belden, Schneider-electric | 22 Eagle 20 Tofino 943 987-501-tx\/tx, Eagle 20 Tofino 943 987-501-tx\/tx Firmware, Eagle 20 Tofino 943 987-502 -tx\/mm and 19 more | 2022-04-09 | 7.5 High |
On Schneider Electric ConneXium Tofino OPCLSM TCSEFM0000 before 03.23 and Belden Tofino Xenon Security Appliance, crafted OPC packets can cause an OPC enforcer denial of service. | ||||
CVE-2021-30062 | 2 Belden, Schneider-electric | 22 Eagle 20 Tofino 943 987-501-tx\/tx, Eagle 20 Tofino 943 987-501-tx\/tx Firmware, Eagle 20 Tofino 943 987-502 -tx\/mm and 19 more | 2022-04-09 | 7.5 High |
On Schneider Electric ConneXium Tofino OPCLSM TCSEFM0000 before 03.23 and Belden Tofino Xenon Security Appliance, crafted OPC packets can bypass the OPC enforcer. | ||||
CVE-2021-30061 | 2 Belden, Schneider-electric | 26 Eagle 20 Tofino 943 987-501-tx\/tx, Eagle 20 Tofino 943 987-501-tx\/tx Firmware, Eagle 20 Tofino 943 987-502 -tx\/mm and 23 more | 2022-04-09 | 6.8 Medium |
On Schneider Electric ConneXium Tofino Firewall TCSEFEA23F3F22 before 03.23, TCSEFEA23F3F20/21, and Belden Tofino Xenon Security Appliance, physically proximate attackers can execute code via a crafted file on a USB stick. | ||||
CVE-2020-25182 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2022-04-05 | 6.7 Medium |
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. | ||||
CVE-2020-25180 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2022-04-04 | 6.5 Medium |
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device. | ||||
CVE-2020-25178 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2022-04-04 | 8.8 High |
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. | ||||
CVE-2020-25176 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2022-04-04 | 9.8 Critical |
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution. | ||||
CVE-2022-24323 | 1 Schneider-electric | 2 Ecostruxure Control Expert, Ecostruxure Process Expert | 2022-03-12 | 5.9 Medium |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Process Expert (V2021 and prior), EcoStruxure Control Expert (V15.0 SP1 and prior) | ||||
CVE-2022-24322 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2022-03-12 | 5.9 Medium |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior) | ||||
CVE-2021-22783 | 1 Schneider-electric | 1 Ritto Wiser Door | 2022-03-12 | 7.6 High |
A CWE-200: Information Exposure vulnerability exists which could allow a session hijack when the door panel is communicating with the door. Affected Product: Ritto Wiser Door (All versions) | ||||
CVE-2022-22813 | 1 Schneider-electric | 66 Easergy P141, Easergy P141 Firmware, Easergy P142 and 63 more | 2022-02-28 | 9.8 Critical |
A CWE-798: Use of Hard-coded Credentials vulnerability exists. If an attacker were to obtain the TLS cryptographic key and take active control of the Courier tunneling communication network, they could potentially observe and manipulate traffic associated with product configuration. | ||||
CVE-2022-22724 | 1 Schneider-electric | 12 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 9 more | 2022-02-25 | 7.5 High |
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions) | ||||
CVE-2021-22796 | 1 Schneider-electric | 1 C-gate Server | 2022-02-23 | 7.8 High |
A CWE-287: Improper Authentication vulnerability exists that could allow remote code execution when a malicious file is uploaded. Affected Product: C-Bus Toolkit (V1.15.9 and prior), C-Gate Server (V2.11.7 and prior) | ||||
CVE-2021-22748 | 1 Schneider-electric | 1 C-bus Toolkit | 2022-02-23 | 8.8 High |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could allow a remote code execution when a file is saved. Affected Product: C-Bus Toolkit (V1.15.9 and prior), C-Gate Server (V2.11.7 and prior) | ||||
CVE-2021-22806 | 1 Schneider-electric | 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more | 2022-02-22 | 7.5 High |
A CWE-669: Incorrect Resource Transfer Between Spheres vulnerability exists that could cause data exfiltration and unauthorized access when accessing a malicious website. Affected Product: spaceLYnk (V2.6.1 and prior), Wiser for KNX (V2.6.1 and prior), fellerLYnk (V2.6.1 and prior) | ||||
CVE-2021-22801 | 1 Schneider-electric | 1 Connexium Network Manager | 2022-02-22 | 9.8 Critical |
A CWE-269: Improper Privilege Management vulnerability exists that could cause an arbitrary command execution when the software is configured with specially crafted event actions. Affected Product: ConneXium Network Manager Software (All Versions) | ||||
CVE-2021-22824 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 7.5 High |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in denial of service, due to missing length check on user-supplied data from a constructed message received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21320 and prior) | ||||
CVE-2021-22823 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 9.1 Critical |
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21320 and prior) |